UPS-BAT/VRLA/24DC/3.4AH
Dimensions
Width 85 mm
Height 191 mm
Depth 110 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) 0 °C ... 40 °C
Ambient temperature (storage/transport) 0 °C ... 40 °C
Max. permissible relative humidity (operation) = 95 %
Degree of pollution 2
Input data
Nominal input voltage 24 V DC
Buffer period 4.5 min. (20 A)
3 min. (25 A)
Output data
Nominal output voltage 24 V DC
Output current Imax 25 A
Connection in parallel 5
Connection in series No
Output fuse 1x 25 A
General
IQ technology Yes
Disposal Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. They can also be returned to Phoenix Contact or the manufacturer.
Net weight 3.3 kg
Memory medium Lead rechargeable battery module
Protection class III
Degree of protection IP20
Mounting position horizontal DIN rail NS 35, EN 60715